Difference between revisions of "Permeable pavements: Specifications"

From LID SWM Planning and Design Guide
Jump to navigation Jump to search
(Created page with "{|class="wikitable" |+ specifications for pervious concrete, porous asphalt, and permeable pavers. |- !style="background: cyan; color: black"|Material !style="background: cy...")
 
Line 1: Line 1:
{|class="wikitable"
{|class="wikitable"
|+ specifications for pervious concrete, porous asphalt, and permeable pavers.
|+ <h2>[[Specifications for pervious concrete, porous asphalt, and permeable pavers]] </h2>


|-
|-
Line 9: Line 9:


!Pervious Concrete
!Pervious Concrete
|* 28 day compressive strength = 5.5 to 20 MPa <br> * Void ratio = 14% - 31%<br>* Permeability = 900 - 21,500 mm/hr||Thickness will range from 100-150 mm depending on the expected loads
|* 28 day compressive strength = 5.5 to 20 MPa <br> * Void ratio = 14% - 31%<br>* Permeability = 900 - 21,500 mm/hr||Thickness will range from 100 mm-150 mm depending on the expected loads
|-
|-
!Porous Asphalt
!Porous Asphalt
|* open-graded asphalt mix with a minimum of 16% air voids <br> * Polymer can be added to provide additional strength to heavy loads||Thickness will range from 50 mm-100 mm depending on the expected loads
|-
!Permeable Pavers
|*ASTM No. 8(5 mm dia) crused aggregate is recommended for fill material in the paver openings.<br>*Pavers shall meet the minimum material and standard specification for Precast Concrete Pavers.<br>*Pigment in concrete pavers shall conform to ASTM C 979 ACI Report No. 212.3R provides guidance on the use of pigments.<br>*Maximum allowable breakage of product is 5%||*For vehicle applications the minimum paver thickness is 80 mm<br>*For pedestrian applications is 60 mm and Joint widths should be no greater than 15 mm.
|-

Revision as of 13:26, 20 September 2017

Specifications for pervious concrete, porous asphalt, and permeable pavers

Material Specification Quantity
Pervious Concrete * 28 day compressive strength = 5.5 to 20 MPa
* Void ratio = 14% - 31%
* Permeability = 900 - 21,500 mm/hr
Thickness will range from 100 mm-150 mm depending on the expected loads
Porous Asphalt * open-graded asphalt mix with a minimum of 16% air voids
* Polymer can be added to provide additional strength to heavy loads
Thickness will range from 50 mm-100 mm depending on the expected loads
Permeable Pavers *ASTM No. 8(5 mm dia) crused aggregate is recommended for fill material in the paver openings.
*Pavers shall meet the minimum material and standard specification for Precast Concrete Pavers.
*Pigment in concrete pavers shall conform to ASTM C 979 ACI Report No. 212.3R provides guidance on the use of pigments.
*Maximum allowable breakage of product is 5%
*For vehicle applications the minimum paver thickness is 80 mm
*For pedestrian applications is 60 mm and Joint widths should be no greater than 15 mm.