Difference between revisions of "Bioretention: Sizing"
Dean Young (talk | contribs) |
Dean Young (talk | contribs) |
||
Line 110: | Line 110: | ||
* Step 7: Sum total depth of bioretention components, and compare to available space (i.e. depth) between the proposed surface grade and the seasonally high water table or top of bedrock elevations in the practice location. | * Step 7: Sum total depth of bioretention components, and compare to available space (i.e. depth) between the proposed surface grade and the seasonally high water table or top of bedrock elevations in the practice location. | ||
* Step 8: Adjust component depths to maintain a separation of 1.0 metre between base of the practice and seasonally high water table or top of bedrock elevation, or a lesser or greater value based on groundwater mounding analysis. See below and [[Groundwater]] for more information.<br> | * Step 8: Adjust component depths to maintain a separation of 1.0 metre between base of the practice and seasonally high water table or top of bedrock elevation, or a lesser or greater value based on groundwater mounding analysis. See below and [[Groundwater]] for more information.<br> | ||
For practices without an underdrain in locations constrained in the vertical dimension, consider decreasing filter media depth (and plant types) and/or catchment area.<br> | For practices without an underdrain in locations constrained in the vertical dimension, consider decreasing filter media depth (and plant types) and/or catchment impervious area.<br> | ||
For practices with an underdrain in locations constrained in the vertical dimension, consider installing perforated pipe on the bottom of the storage reservoir and including a riser (saves the depth of aggregate needed to embed the pipe), and/or decreasing filter media depth (and plant types), ponding depth and/or catchment area. | For practices with an underdrain in locations constrained in the vertical dimension, consider installing perforated pipe on the bottom of the storage reservoir and including a riser (saves the depth of aggregate needed to embed the pipe), and/or decreasing filter media depth (and plant types), ponding depth and/or catchment impervious area. | ||
==Determine the required surface area of the practice== | ==Determine the required surface area of the practice== |
Revision as of 21:15, 4 May 2020
This article is specific to bioretention, vegetated systems that infiltrate water to the native soil.
If you are designing a planted system which does not infiltrate water, see advice on Planters: Sizing.
Many of the dimensions in a bioretention system can be predetermined according to the function of the component. There is greatest flexibility in the ponding depth and the depth of the storage reservoir beneath the optional underdrain pipe. The table below describes some recommended values to use to begin the design process.
Component | Recommended depth (with underdrain pipe) | Recommended depth (no underdrain pipe) | Typical porosity (n) |
---|---|---|---|
Surface ponding, maximum (dp, max) |
|
See below | 1 |
Mulch | 75 ± 25 mm |
| |
Filter media (dm) |
|
| |
Choker layer | 100 mm | 0.4 | |
Perforated pipe and surrounding aggregate | 200 mm (i.e. pipe diameter) | Not applicable | 0.4 |
Storage reservoir (ds) | See below | See below | 0.4 |
Before you begin you will need to know the following;
- Catchment area (i.e. contributing drainage area), Ac (m2)
- Catchment impervious area, Ai (m2)
- Catchment runoff coefficient, C
- Design storm intensity, i (mm/h)
- Design storm duration, D (h)
- Infiltration target for design storm event, Id (mm)
- Drainage time t (h) to fully drain the active storage of the practice, based on provincial or municipal criteria or average inter-event period for the location
- Field infiltration rate of the underlying native soil ff (mm/h), median of field measurements or based on interpolation from median grain-size distribution results
- Design infiltration rate of the underlying native soil f' (mm/h), median field measured value divided by a safety factor (z)
- Safety factor, z (dimensionless value between 2 and 3) chosen by designer based on consideration of risk of failure factors
- Proposed surface grade elevation at the practice location (metres above sea level, masl)
- Elevation of the seasonally high water table or bedrock surface (metres above sea level, masl), below the practice location
- Effective porosity of any void-producing structure system (e.g. soil cells, chambers and associated aggregate) included, n' (if applicable)
- Types of plants to be supported by the filter media bed (i.e. grasses vs. mix of grasses, plants and shrubs vs. trees)
- How runoff will be delivered to the practice (i.e. to filter bed surface; to storage reservoir; or both)
Decide if an underdrain will be included[edit]
- Step 1: Based on the median measured infiltration rate of the native soil at the estimated location and bottom elevation of the practice, or estimated from the median grain-size distribution results, decide if an underdrain will be included in the design.
If the field estimated infiltration rate of the underlying native soil (ff) is less than 15 mm/h, include an underdrain.
Select a surface ponding depth to begin sizing with[edit]
- Step 2: Determine a maximum surface ponding depth (dp, max)
For practices without underdrains:
Where:
- f' = Design infiltration rate (mm/h), and
- 48 = Maximum permissible drainage time for ponded water (h)
- Note that in designs without underdrains, conceptually the drainage of ponded water is limited by infiltration through the base of the practice.}}
For practices with underdrains see recommended maximum surface ponding depth for each filter media blend in the table above.
- Step 3: Select a design surface ponding depth, dp' (m) to begin sizing with:
For practices with soft (i.e. landscaped) edges and bowl-shaped ponding areas calculate the mean surface ponding depth:
Where:
- dp, max = maximum surface ponding depth (m)
For practices with hard edges and vertical-walled ponding areas (e.g., stormwater planter, soil cell) use the maximum ponding depth:
Determine the active water storage depth of the practice[edit]
- Step 4: Identify the active water storage of the practice, da
For practices without an underdrain, the active water storage components include the surface ponding, mulch and filter media depths (i.e. total depth of the practice). The active water storage depth of the practice can be calculated as:
Where:
- dp' = Design surface ponding depth (m)
- dm = Depth of mulch (m)
- nm = Porosity of mulch
- df = Depth of filter media (m)
- nf = Porosity of filter media
For practices with the underdrain perforated pipe elevated off the bottom of the storage reservoir, the active storage component is the depth of storage reservoir below the invert of the underdrain perforated pipe that can reliably drained within the specified drainage time. The active water storage of the practice can be calculated as:
Where:
- f' = Design infiltration rate of underlying native soil (m/h)
- t = Drainage time (h). Check provincial or local criteria for drainage time requirements
For practices with the underdrain perforated pipe installed on the bottom of the storage reservoir and connected to a riser (e.g., standpipe and 90 degree coupling), the active storage component is the storage reservoir depth between the inverts of the reservoir bottom and riser outlet (i.e invert elevation of the 90 degree coupling) and is calculated the same way as above.
To boost drainage performance on fine-textured, low permeability soils, consider designing storage reservoirs even deeper than those calculated using the above approach, that many not fully drain between storm events, which increases hydraulic head and infiltration rate at the base of the practice. See Low permeability soils for more information.
Calculate the total depth of the practice, dT[edit]
- Step 5: Determine what the planting needs are and assign an appropriate depth of filter media, using the table above.
- Step 6: Select an underdrain perforated pipe diameter (typically 100 - 200 mm), assign this as an 'embedded' depth equal to the pipe diameter. *Note that this component does not apply if a downstream riser is being used to create the storage reservoir.
- Step 7: Sum total depth of bioretention components, and compare to available space (i.e. depth) between the proposed surface grade and the seasonally high water table or top of bedrock elevations in the practice location.
- Step 8: Adjust component depths to maintain a separation of 1.0 metre between base of the practice and seasonally high water table or top of bedrock elevation, or a lesser or greater value based on groundwater mounding analysis. See below and Groundwater for more information.
For practices without an underdrain in locations constrained in the vertical dimension, consider decreasing filter media depth (and plant types) and/or catchment impervious area.
For practices with an underdrain in locations constrained in the vertical dimension, consider installing perforated pipe on the bottom of the storage reservoir and including a riser (saves the depth of aggregate needed to embed the pipe), and/or decreasing filter media depth (and plant types), ponding depth and/or catchment impervious area.
Determine the required surface area of the practice[edit]
- Step 10: Calculate the surface (i.e footprint) area of the practice (Ap) needed to capture the runoff volume produced from the catchment during the design storm event
For practices where flow is delivered to the filter media bed:
Where:
- i = Design storm intensity (m/h)
- D = Design storm duration (h)
- Ai = Catchment impervious area (m2)
- dp' = Design surface ponding depth (m)
- fm, min = minimum infiltration rate (i.e. saturated hydraulic conductivity) of the filter media (m/h), see Filter media for guidance
For practices where flow is delivered to the storage reservoir:
Where:
- da = Active storage depth (m)
- n = porosity of storage reservoir aggregate or effective porosity of void-producing structure system
- f' = design infiltration rate of the underlying native soil (m/h)
- D = Design storm duration (h)
Calculate peak flow rates[edit]
- Step 13. Calculate the peak flow rate through the perforated pipe,
- Step 14. Calculate the peak flow rate through the filter media,
- Step 15. Determine if downstream flow control is required to achieve hydrologic objectives.
Calculating infiltration practice drainage in 1 dimension[edit]
This spreadsheet compares drainage in a single dimension under zero head conditions, mean head conditions and falling head conditions. It provides a more conservative measurement of the drainage time for the purposes of groundwater mounding (where a shorter drainage time causes a greater impact).
Drainage time (3D)[1][edit]
In some situations, it may be desirable to reduce the size of the bioretention required, by accounting for rapid drainage. Typically, this is only worth exploring over sandy textured native subsoils with rapid infiltration.
Note that narrow, linear bioretention features (or bioswales) drain faster than round or blocky footprint geometries.
- Begin the drainage time calculation by dividing the area of the practice (Ap) by the perimeter (x).
- To estimate the time (t) to fully drain the facility:
Where:
- n is the porosity of the filter media,
- Ap is the area of the practice (m2),
- f' is the design infiltration rate (mm/hr),
- x is the perimeter of the practice (m), and
- dT is the total depth of the practice, including the surface ponding depth (m).
Groundwater mounding[edit]
When you wish to model the extent of groundwater mounding beneath an infiltration facility. This tool uses Hantush's derivation (1967).
Note that this is a minor adaptation (metric units and formatting) from the original tool, written and hosted by the USGS.
- ↑ Woods Ballard, B., S. Wilson, H. Udale-Clarke, S. Illman, T. Scott, R. Ahsley, and R. Kellagher. 2016. The SuDS Manual. 5th ed. CIRIA, London.